Evaluating an HP/IP Turbine Replacement

By Bill Kettenacker, P.E., Scientech

Many U.S. power producers are stretching the useful lives of their existing power plants because of the favorable economics as compared to other alternatives. Environmental issues, licensing delays, public outcry and structural costs top the list of reasons for delaying, canceling or even considering planned and future generation projects. The U.S. power plant fleet is aging, as well, with many plants 30 years old or older.

Click here to enlarge image

To extend the life of these aging plants, power producers are refurbishing or replacing older systems and equipment to prolong life, increase efficiency, lower emissions, save money and squeeze the last ounce of power from these assets.

Because of new technologies developed in recent years, the replacement equipment being installed is more efficient than the existing equipment ever was, even when it was brand new. However, how will this new technology improve plant performance? Just as important, how will it affect the plant’s older systems and components?

To determine how new equipment will perform and interact with the existing older equipment before any contracts are signed, power producers are using analytical techniques that are often beyond those offered by equipment manufacturers. These independent checks have proven valuable to power producers and have uncovered some surprising results.

As one example of equipment replacement at an older plant, in 2007 a large U.S. utility sought to replace the high pressure (HP) and intermediate pressure (IP) turbines at one of its 300 MW coal-fired units to increase plant efficiency and raise generation “without burning one more pound of coal,” as an executive of that utility stated.

Requests for bid were sent to various turbine manufacturers, with two manufacturers responding with proposals. To verify each vendor’s performance claim and to determine the new turbines’ effect on the rest of the unit, the utility used the PEPSE (performance evaluation of power system efficiencies) heat balance software program, employing a PEPSE simulation model of the unit’s turbine and boiler systems.

Based on the results of a PEPSE analysis of the proposed new turbines, the turbine manufacturers’ proposals did indeed meet their performance guarantees. However, because the new turbines were more efficient than the existing HP and IP turbines, they removed more energy from the steam than the existing HP and IP turbines, leaving less energy available for the downstream low pressure (LP) turbine. The net effect was an increase in the HP and IP turbine output, but a decrease in LP turbine output. While an overall increase in unit output occurred, it was lower than expected after factoring in the decreased output of the now energy-starved LP turbine.

Click here to enlarge image

Additional PEPSE analyses were performed. In one case, rebuilt HP and IP turbines, rather than new turbines, were analyzed. As expected, the rebuilt turbines were not as efficient and did not produce as much additional power as the proposed new turbines, but their cost vs. new turbines was significantly lower. Finally, various additions to boiler surface area in the superheat (primary and secondary), reheat and economizer sections were analyzed using the new turbines.

The utility performed a cost/benefit analysis based on the PEPSE results. Their three turbine options included: 1) do nothing, 2) replace the HP and IP turbines with new turbines and 3) rebuild the HP and IP turbines. Their various boiler surface area choices included superheat, reheat and/or economizer surface area additions. The results of this cost/benefit analysis encouraged rebuilding the turbines at the next major outage rather than replacing with new equipment. What’s more, the utility will forgo any boiler surface additions.

The Unit

The power generating facility under study is one unit of a multiple-unit plant. It was designed to produce 310 MWe at full load conditions of 2 x 106 lb/hr main steam flow, 1,050 F main steam temperature, 2,400 psig main steam pressure and 1,000 F reheat temperature. This unit first came online in the early 1970’s.

The boiler continues as its original design built by Combustion Engineering. It burns pulverized coal purchased from a variety of sources, including term contracts and the spot market.

The current HP, IP and LP turbines were built by General Electric. The unit is a cross-compound arrangement, with single-flow HP and IP turbines powering one 3,600 rpm generator and a double-flow LP turbine powering one 1,800 rpm generator. There are seven feedwater heaters in the cycle.

The Problem

Having the original HP and IP turbines from the early 1970’s made their improvement or replacement a key issue at the plant. Their deteriorating performance and increased maintenance were primary factors contributing to a heightened focus on these turbines. New turbine technologies offering higher efficiencies, in addition to environmental issues and rising energy costs, also contributed to the decision to explore options for the turbines. A major outage already planned for 2010 would allow enough lead time to plan any project involving the turbines and sufficient plant downtime to install the new turbines.

The Solution

In early 2007, the utility sent a request for proposals to various turbine manufacturers with specifications requiring replacement of the HP and IP turbines. Two turbine manufacturers, or original equipment manufacturers (OEM’s), responded with quotations and performance specifications for proposed new turbines. For both respondents, the primary performance specification was a single heat balance diagram. This diagram showed the new HP and IP turbines. However, the performance of other components and systems, including the system boundary conditions, were unchanged from the original 1970’s-vintage turbine vendor heat balance diagram. While a heat balance diagram may be a basis for the turbine manufacturers’ guarantees, it does not reflect adequately how the new turbines will perform in the plant today. Component performances are usually different, either through their own deterioration or replacement over the years. Turbine cycle boundary conditions such as steam properties from the boiler may also be different for the same reasons. Other conditions, for a variety of reasons, may have also changed. Guarantees are one thing, but what’s the real story?

The Evaluation

Actual turbine and plant performance can only be learned after the turbines are installed and tested in the plant. However, a close approximation of that performance can be derived by performing a system analysis using one of the available heat balance programs currently on the market. This utility chose PEPSE because of their long history with this software program.

PEPSE is a steady-state energy balance software program that calculates the performance of the plant. This plant analysis is done using a model that mimics the actual plant configuration. A model is developed in a Windows interface setting by dragging and dropping plant component icons onto the screen from a component library. This library contains all the component types found in any power plant including turbine cycle systems for nuclear plants and fossil plants, fossil boilers, gas turbines, combined cycles, cogeneration plants and any other process steam or other fluid system.

PEPSE models of this unit’s turbine cycle and boiler have existed for years. However, they were modified for this analysis to account for current plant data. With PEPSE, these models were developed and tuned separately, then combined using one of PEPSE’s special features.

A second model was developed for this study—a submodel of the HP and IP turbines only (see Figure 2). This submodel allowed the input and tuning of each of the two OEM’s turbine performance claims to be analyzed without influence from the other components and systems in the cycle. Recall that these other components and systems were left unchanged in the OEM’s newly proposed turbine cycle heat balances as compared to the original heat balance. Then, after running and tuning the turbines using this submodel, the tuning parameters were transferred to the main turbine model. The result is a PEPSE model of the unit’s boiler and turbine cycles tuned to current plant data but using each of the OEM’s proposed new turbines.

Click here to enlarge image

null

The Results

Results of the PEPSE analysis showed that the replacement turbines for both OEM’s behaved as proposed. However, the new turbines removed much more energy from the steam than the original turbines, thus energy-starving the LP turbine. This caused the LP turbine output to decrease. The net effect for both OEMs compared to current plant operation was an increase in the HP and IP generation of about 11 MW, but a decrease in the LP generation of about 5 MW. This gave a net increase of about 6 MW. These results, showing such a small net increase in the total plant output, caused the turbine replacement project to look much less attractive than originally thought. Results are summarized in Table 1, columns B and C for the two turbine manufacturers compared to current operations in column A. In an attempt to keep the turbine replacement project alive, various boiler modifications were suggested by the utility and investigated using PEPSE. The most practical involved increasing the surface area of some of the boiler sections. This would possibly allow more energy transfer from the boiler to the turbine cycle through main steam and reheat, potentially making up for the energy lost going to the LP turbine. The PEPSE model was again used, this time to investigate increases in boiler superheat (both primary and secondary), reheat and economizer surface along with the turbine replacement. This involved adding rows of tubes to these boiler sections in the PEPSE boiler model. Additions of 5 percent to 25 percent were investigated. As a practical matter, an increase of 25 percent is virtually impossible due to space limitations in the boiler backpass. A practical limit of 10 percent was considered more realistic and used as the basis for comparisons. Each boiler section’s tube row increase was analyzed separately; that is, no two sections were increased at the same time.

Click here to enlarge image

Two separate versions of the boiler tube row increase analysis were performed. The first was with no superheat or reheat temperature control; that is, the fuel flow remained constant at its current plant operating value at 100 percent load. Second, the fuel flow was adjusted to maintain temperature control at the original design values of 1,050 F main steam temperature and 1,000 F reheat temperature.

The results of this boiler surface PEPSE analysis using the proposed new turbines showed very small increases in generation over that with just the new turbines alone, about 1 MW or less. The results with no temperature control are presented in Table 2 (OEM 1) and Table 3 (OEM 2). Those results with temperature control appear in Table 4 (OEM-1 only). Results with temperature control for OEM-2 show about the same differences when compared with OEM-1 as they did with no temperature control.

Click here to enlarge image

 

Click here to enlarge image

 

Click here to enlarge image

 

 

The results of the boiler surface area study were inconclusive relative to whether the turbine replacement was feasible. One more analysis was performed with the PEPSE model, this time looking at rebuilt HP and IP turbines rather than new turbines. Rebuilt turbines represent a lower cost/lower return alternative when compared to new turbines.

Turbine performance characteristics based on the utility’s best estimate of rebuilt turbines (83.5 percent efficiency for the HP turbine, 90 percent efficiency for the IP turbine) were used in the PEPSE model. Just using rebuilt turbines (no boiler surface changes), the PEPSE model results showed that the HP and IP output collectively increased by about 4 MW and the LP output decreased by about 2 MW. This resulted in a net output gain of about 2 MW. These results are shown in Table 5, column B alongside current operations shown in column A.

Click here to enlarge image

Finally, this PEPSE analysis continued using these rebuilt turbines and including temperature control to the original design values of 1,050 F main steam temperature and 1,000 F reheat temperature. These results are presented in Table 5, column C.

The Decision

With all the performance numbers in and all the feasible scenarios analyzed, what remained was to put dollars to the numbers to determine the best cost/benefit. Looking at upfront expenses, replacing the HP and IP turbines costs about $12 million. Rebuilding the turbines instead of replacing them runs about $1.5 million. Doing nothing costs $0.

But what about later? Here the paybacks are reversed, with the new turbine option paying back the most, doing nothing paying the least and the rebuild somewhere in the middle.

The utility’s decision after careful and detailed analysis was to rebuild the turbines during the next major outage. No additional boiler surface will be added.

Author: Bill Kettenacker, P.E., is the PEPSE Project Manager at Scientech, a division of Curtiss-Wright Flow Control Service Corp. He is an original author and major contributor to the development of the PEPSE software. He has over 30 years of experience in the electric utility industry.

Sponsored by FLSmidth
Recommend this article Recommend this article () You recommended this article You recommended this article ()
Follow Power Engineering on Twitter

Products Showcase

Dynamic Fluoride Ion cleaning DFIC of industrial natural gas turbines Hi-Tech Furnace Systems

Dynamic Fluoride Ion Cleaning of IGT Parts

The Dynamic Fluoride Ion Cleaning (DFIC) Process from Hi-Tech Furnace Systems is able to clean deep, narrow cracks of oxides by cycling between negative, atmospheric, and positive pressure.

Latest News

Shutterstock coal production trucks

Weekly Coal Production

The Weekly Coal Production shows how much coal is being produced across the U.S.

Federal Reserve Bank of Dallas Weekly Economic Indicators financial business

The Federal Reserve Bank of Dallas' Economic Indicators

The Federal Reserve Bank of Dallas offers a glimpse into how the markets are doing domestical...

Kvaerner awarded contract for gas-fired power plant in Delaware

Kvaerner North American Construction Inc. and its joint venture partner, Parsons Brinckerhoff...

Canadian Solar purchases two solar projects

Canadian Solar Inc. has acquired a majority interest in two utility-scale solar power project...

Operators Restart Unit 2 at PPL Susquehanna

Unit 2 at the PPL Susquehanna nuclear power plant near Berwick, Pa. resumed generating electr...

Settlement agreement limits cost recovery at Edwardsport

The Indiana Utility Regulatory Commission (IURC) on Dec. 27 modified and approved a settlemen...

Toshiba in talks to sell portion of Westinghouse nuclear unit

Toshiba Corp is in talks  to sell up to 16% of its stake in the Westinghouse Electric Co...

Utah nixes nuclear waste storage facility

Plans to park radioactive waste at a storage facility in Utah have been officially called off.

Archived Articles

2000 | 2001 | 2002 | 2003 | 2004 | 2005 | 2006 | 2007 | 2008 | 2009 | 2010 | 2011 | 2012 | 2013

Current Magazine Issue

08/01/2013
Volume 117, Issue 8
1308PE_C1_digital

Power Industry Wire News

Signal Hill Petroleum Named Finalist for 2014 Company of the Year Award

Signal Hill Petroleum Named Finalist for 2014 Company of the Year Award

Algae Biomass Summit Showcases Innovation in Algae Engineering

Algae Biomass Summit Showcases Innovation in Algae Engineering

TVRM's Historic Steam Locomotive #4501 Is Ready for Tennessee Valley Railfest

TVRM's Historic Steam Locomotive #4501 Is Ready for Tennessee Valley Railfest

Quantum Energy Signs Two Year Option on 144 Acre Refinery Site

Quantum Energy Signs Two Year Option on 144 Acre Refinery Site

Viking Investments Group, Inc. Announces Commitment Toward Private Placement

Viking Investments Group, Inc. Announces Commitment Toward Private Placement

Power Engineering

Article Archives for Power Engineering Magazine

Continuing Education

Professional Development Hours

To access a course listing associated to a specific topic listed below, click on the topic of choice from the list below.

Latest Energy Jobs

View more Job Listings >>